IIR document

Thermodynamic studies on NH3-H2O absorption cooling system using pinch point approach.

Author(s) : JAWAHAR C. P., RAJA B., SARAVANAN R.

Type of article: Article, IJR article

Summary

An ammonia-water (NH3-H2O) absorption cooling system is analyzed using the pinch point analysis, to recover maximum internal heat from the streams, thereby increasing the system performance. The system is simulated for generator temperatures between 120 and 150°C, sink temperatures between 25 and 45°C and evaporator temperatures between -10 and 10°C. Based on the maximum internal heat that could be obtained using this approach the conventional cycle is modified without the need for rectification and its performance is compared. The COP of the proposed cycle is found to be 17 to 56% higher than that of a conventional cycle with respect to the operating conditions analyzed.

Available documents

Format PDF

Pages: pp. 1377-1385

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Thermodynamic studies on NH3-H2O absorption cooling system using pinch point approach.
  • Record ID : 2010-1138
  • Languages: English
  • Subject: Regulation
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 7
  • Publication date: 2010/11