Transcritical industrial heat pump using HFO’s for up to 150°C hot air supply.

Number: pap. n. 1184

Author(s) : ABI CHAHLA G., BEUCHER Y., ZOUGHAIB A., et al.

Summary

Heat pumps may be used in drying processes to recover low-grade heat contained in moist exhaust air and supply the dryer. The heat pump design is limited technically by the level of process temperature and its performance optimization depends strongly on the difference between both temperature levels of process and effluents. Using an exergy optimization methodology for heat pump integrations in industrial processes, a high temperature transcritical heat pump using the R-32 as working fluid was earlier proposed by the authors and experimentally demonstrated a 120°C hot air supply temperature. In this paper, HFO’s are considered to increase the air supply temperature to reach up to 150°C. Architecture technical options are also studied in order to improve the COP depending on the heat source and sink properties. The prototype developed for the R-32 is adapted and used to validate the predicted performances. Its performance, when heating air from 90°C or 100°C to 150°C, is presented. The effluents are available at 82°C with different absolute humidities. The observed COP of the heat pump reached up to 3.72.

Available documents

Format PDF

Pages: 8

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Transcritical industrial heat pump using HFO’s for up to 150°C hot air supply.
  • Record ID : 30026520
  • Languages: English
  • Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Publication date: 2019/08/24
  • DOI: http://dx.doi.org/10.18462/iir.icr.2019.1184

Links


See other articles from the proceedings (632)
See the conference proceedings