IIR document

Enhancement of heat pump performance by pulsation of refrigerant flow using a solenoid-driven control valve.

Author(s) : ROH C. W., KIM M. S.

Type of article: Article, IJR article

Summary

The heating performance of an R410A heat pump system can be enhanced by a pulsatile refrigerant flow in a heat pump cycle. To generate the pulsatile refrigerant flow, a control valve was installed in parallel with the expansion valve located between the outlet of the condenser and the inlet of the evaporator in this system. Intermittent 200-ms openings of the control valve improved the heating performance because of two factors: the ‘pulsation effect’ that enhanced heat transfer and the ‘pushing effect’ that elevated the condensing pressure and increased overall mass flow rate. Heating capacity and COP (coefficient of performance) were increased by 4 and 3.2%, respectively, when the control valve operated at 0.005 Hz and 0.1% duty. In phenomenological view, two-phase invasion is considered when the control valve is operated.

Available documents

Format PDF

Pages: 1547-1557

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Enhancement of heat pump performance by pulsation of refrigerant flow using a solenoid-driven control valve.
  • Record ID : 30004795
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 6
  • Publication date: 2012/09

Links


See other articles in this issue (28)
See the source