Experimental comparison of R22 and new-generation refrigerant mixtures : R407C and R410A.

Un confronto sperimentale tra il refrigerante R22 e le miscele di nueva generazione R407C ed R410A.

Author(s) : BASILE G., MUSSO E., ZILIO C.

Summary

The performance of R407C (COP and refrigerating capacity) is almost equivalent to that of R22. Nevertheless, this work has shown that the decrease of COP with evaporation temperature around -20 °C is greater in the case of R407C. As for R410A, the COP is lower than that of R22 in the ideal cycle, but higher in the real cycle.

Details

  • Original title: Un confronto sperimentale tra il refrigerante R22 e le miscele di nueva generazione R407C ed R410A.
  • Record ID : 2000-2396
  • Languages: Italian
  • Source: Le ultime tecnologie del freddo e del condizionamento./ Latest technologies in refrigeration and air conditioning.
  • Publication date: 1999/06/18
  • Document available for consultation in the library of the IIR headquarters only.

Links