Experimental investigation of multi-functional variable refrigerant flow system.

Number: pap. 2375

Author(s) : LIN X., LEE H., HWANG Y., et al.

Summary

The variable refrigerant flow (VRF) systems have a broader flexibility in control and a wider range of capacity modulation. In this study, a multi-functional VRF (MFVRF) system, which is capable of heat recovery operation and water heating, was experimentally investigated. The MFVRF system could supply space cooling and heating simultaneously in multiple zones, as well as provide hot water. The system’s performance during the experiment was measured and discussed. We found that the partial load performance of the system was improved with water heating capability, which increased the daily performance factor (DPF) by 17 percent. We also found that the system performance was enhanced by a heat recovery operation, which could increase the hourly performance factor (HPF) by reducing the pressure differences across the compressor.

Available documents

Format PDF

Pages: 10 p.

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental investigation of multi-functional variable refrigerant flow system.
  • Record ID : 30013562
  • Languages: English
  • Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Publication date: 2014/07/14