Identifying and evaluating alternatives to CFC-114 for navy shipboard chillers.

Author(s) : BARE J. C.

Type of article: Article

Summary

About 850 CFC-114 water chillers are installed in US naval ships. A program to identify an alternative refrigerant for simple retrofitting was essential. From a list of 34 promising chemicals, the hexafluoropropane isomers HFC-236ea and HFC-236fa were selected. Tests to date indicate thermodynamic properties reasonably similar to CFC-114, and toxicity, flammability and compatibility with used materials appear to be acceptable. A polyolester lubricant would be required. Additional tests such as acceptability in submarine situations may still be needed. D.W.H.

Details

  • Original title: Identifying and evaluating alternatives to CFC-114 for navy shipboard chillers.
  • Record ID : 1997-1344
  • Languages: English
  • Source: ASHRAE Journal - vol. 38 - n. 1
  • Publication date: 1996/01
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (1)
See the source