IIR document

METHODS FOR COMPARING THE PERFORMANCE OF PURE AND MIXED REFRIGERANTS IN THE VAPOUR COMPRESSION CYCLE.

Author(s) : MCLINDEN M. O., RADERMACHER R.

Type of article: Article, IJR article

Summary

TO COMPARE PURE AND MIXED REFRIGERANTS THE COP AND THE HEATING CAPACITY FOR AN IDEAL COMPRESSION CYCLE FOR R22/R114 AND R22/R11 MIXTURES WERE COMPUTED. FOR COMPARISONS BASED ONLY ON ONE CHARACTERISTIC CONDENSATION TEMPERATURE AND ONE EVAPORATION TEMPERATURE, THE RESULTS DEPEND ENTIRELY ON HOW THE CHARACTERISTIC TEMPERATURES ARE DEFINED. A METHOD SPECIFYING THE HEAT TRANSFER FLUID TEMPERATURES AND A TOTAL EXCHANGER AREA PER UNIT CAPACITY IS PROPOSED. THE EFFECTS OF COMPRESSOR SUPERHEAT, HEAT EXCHANGER APPROACH TEMPERATURES, AND THE MATCH OF REFRIGERANT AND HEAT TRANSFER FLUID TEMPERATURES ARE DISCUSSED.

Available documents

Format PDF

Pages: 318-325

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: METHODS FOR COMPARING THE PERFORMANCE OF PURE AND MIXED REFRIGERANTS IN THE VAPOUR COMPRESSION CYCLE.
  • Record ID : 1988-1340
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 10 - n. 6
  • Publication date: 1987

Links


See other articles in this issue (8)
See the source