Modeling and optimization of R-717 and R-134a ice thermal energy storage air conditioning systems using NSGA-II and MOPSO algorithms.
Author(s) : RAHDAR M. H., HEIDARI M., ATAEI A., et al.
Type of article: Article
Summary
In this study, an Ice Thermal Energy Storage (ITES) is integrated to an office building air-conditioning system as a full load storage system. The R-134a and R-717 refrigeration systems by exergy, economic and environmental considerations are modeled and investigated separately. Two multi-objective optimization algorithms: Non-dominated Sorting Genetic Algorithm-II (NSGA-II) and Multi-Objective Particle Swarm Optimization (MOPSO), are engaged to obtain the optimal design parameters which lead to the optimal objective functions, exergy efficiency and total cost rate. The optimum point from Pareto frontier of each optimization algorithm is selected for both refrigerants by using TOPSIS decision making method, and energy demand of the new system is compared to the conventional one. The results indicated that by using NSGA-II and MOPSO algorithms for the R-717 refrigerant based system, the optimum design parameters lead to electricity consumption decrease by 11% and 8% more than R-134a refrigerant based system, respectively. Furthermore, the results showed that NSGA-II is more capable to achieve more effective solutions. At the optimum point of NSGA-II for R-717 based system, the exergy efficiency and total cost rate are 49% and 255USDh-1 respectively. While the annual CO2 emission is 11% lower than the R-134a based system.
Details
- Original title: Modeling and optimization of R-717 and R-134a ice thermal energy storage air conditioning systems using NSGA-II and MOPSO algorithms.
- Record ID : 30016696
- Languages: English
- Source: Applied Thermal Engineering - vol. 96
- Publication date: 2016/03/05
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2015.11.068
Links
See other articles in this issue (32)
See the source
Indexing
-
Themes:
HFCs;
Ammonia;
Comfort air conditioning;
Chillers - Keywords: R134a; Office; Ammonia; Performance; Optimization; Modelling; Refrigerant; Air conditioning; Thermal energy storage
-
Evaluation of optimal control for active and pa...
- Author(s) : HENZE G. P., FELSMANN C., KNABE G.
- Date : 2004/02
- Languages : English
- Source: International Journal of thermal Sciences - vol. 43 - n. 2
View record
-
Development of optimal operation schemes for HV...
- Author(s) : YAMAGUCHI H., YOSHIDA H.
- Date : 2005/12
- Languages : English
- Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 105
View record
-
State of the art: technology of the room air co...
- Author(s) : ASHITOMI H.
- Date : 2014/02
- Languages : Japanese
- Source: SHASE - vol. 88 - n. 2
View record
-
Ammonia vs. R134a in central plant chiller syst...
- Author(s) : PORT R. P. Jr
- Date : 2003/08
- Languages : English
- Source: HPAC Engineering - vol. 75 - n. 8
View record
-
A comparative study on PCM and ice thermal ener...
- Author(s) : RAHDAR M. H., EMAMZADEH A., ATAEI A.
- Date : 2016/03/05
- Languages : English
- Source: Applied Thermal Engineering - vol. 96
View record