Numerical investigation on integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers.

Author(s) : ZHANG H., SHAO H., XU H., et al.

Type of article: Article, IJR article

Summary

The cooling energy consumption of data centers is increasing rapidly and free cooling attracts growing concern. To achieve the independent running of free cooling system all the year round, integrated system of mechanical refrigeration and thermosyphon (ISMT) is an ideal method. In this study, a distributed-parameter simulation model of an ISMT is built and validated by experimental data. The simulation results show that for thermosyphon mode, the cooling capacity increases with increasing air flow rate, temperature difference and pipe diameter, while decreases with increasing pipe length. For refrigeration mode, decreasing outdoor air temperature or increasing indoor air flow rate will improve the cooling capacity and reduce the input power of the compressor. For dual mode, applicable outdoor temperature range and indoor air flow rate range exist and the cooling capacity drops below that of refrigeration mode beyond these ranges. The critical values are 19?°C and 0.5?m3?s-1, respectively.

Available documents

Format PDF

Pages: 9-18

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Numerical investigation on integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers.
  • Record ID : 30016260
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 60
  • Publication date: 2015/12