IIR document

Performance comparison of the hydrocarbon R290 with R22 in a residential heat-pump system.

Summary

To provide a clearer comparison, the performance potential of R290 was experimentally compared with R22 under a wide range of test conditions. From the experimental comparison of R290 with R22 using an 11% larger R290 compressor, it was found that the cooling performance of R290 approached that of R22 within 2-4%. The heating performance of R290 was up to 11% lower than R22 when the ambient temperature was higher than -20 °C. However, the heating performance of R290 exceeded that of R22 when the ambient temperature dropped below -20 °C.

Available documents

Format PDF

Pages: 2002-5

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance comparison of the hydrocarbon R290 with R22 in a residential heat-pump system.
  • Record ID : 2003-2548
  • Languages: English
  • Publication date: 2002/09/17
  • Source: Source: Proc. 5th IIR-Gustav Lorentzen Conf. nat. Working Fluids, Guangzhou/ C. R. Conf. Guangzhou, IIF
    2002-5; sess. 4; pap. 65; 499-506; fig.; tabl.; 9 ref.