IIR document

Replacement of R22 in tube-and-shell condensers: experiments and simulations.

Author(s) : GABRIELII C., VAMLING L.

Type of article: Article, IJR article

Summary

An investigation of the change in condenser overall heat transfer coefficient when replacing R22 with one of the three mixtures R407C, R404A and R410B was made, both experimentally and theoretically. Measurements have been carried out on a full-scale test plant consisting of a horizontal shell-side condenser. According to the measurements the decrease in overall heat transfer coefficient for the non-azeotropic mixture R407C was very large, up to 70% compared to R22, while for the near-azeotropic mixture R404A the decrease was less than 15%. Simulations of the condenser were done with a comprehensive computer program, calculating the condensation heat transfer with an approximate method including a correction for mass transfer resistance. The calculation model was not able to predict this large degradation for mass transfer resistance. The calculation model was not able to predict this large degradation for the non-azeotropic mixture, while the predictions agreed rather well with the measurements for the pure fluid and the near-azeotropic mixtures.

Available documents

Format PDF

Pages: 165-178

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Replacement of R22 in tube-and-shell condensers: experiments and simulations.
  • Record ID : 1997-2816
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 20 - n. 3
  • Publication date: 1997/05

Links


See other articles in this issue (5)
See the source