Heat generation of datacenters becomes larger and larger because of the improvement of operational performance of equipment and the expansion of datacenter scale. Two-­phase closed-­ loop thermosyphon system as a new type of cooling system, which has a large cooling capacity, has gotten a widespread attention. This paper investigates experimentally heat transfer performance of
a closed-­loop thermosyphon system by testing under different mass concentrations, heating and cooling scenarios. The system, filled with microencapsulated phase change material suspension (MPCMS), contains heating, cooling and adiabatic sections. The result shows that the convective heat transfer coefficient at the heating section inlet with 0.5% MPCMS is twice as much as that of
base fluid. Hence, a closed-­loop thermosyphon system with MPCMS is an effective scheme to enhance the performance of the cooling system.

Available documents

Format PDF

Pages: 8

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Research on heat transfer of the closed-loop thermosyphon system with microencapsulated phase change material suspension.
  • Record ID : 30026475
  • Languages: English
  • Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Publication date: 2019/08/24
  • DOI: http://dx.doi.org/10.18462/iir.icr.2019.0719

Links


See other articles from the proceedings (632)
See the conference proceedings