Experimental study on a four-stage auto-cascade refrigeration system with the temperature down to -150°C.

Author(s) : XIAO C. J., ZHANG H., LIU H. S., et al.

Summary

A four-stage auto-cascade refrigeration cycle is developed and the experimental rig is set up. The blend of refrigerants used was a mixture of R600a/R23/R14/R740. The reasonable proportion of the blend refrigerants is determined. The temperature in the centre of the freezer decreases successfully down to -150°C. Refrigerant temperatures after throttling were tested and analysed. The effect of the proportion of the blend refrigerants on the refrigeration temperature is concluded.

Details

  • Original title: Experimental study on a four-stage auto-cascade refrigeration system with the temperature down to -150°C.
  • Record ID : 2009-0097
  • Languages: English
  • Source: Cryogenics and refrigeration. Proceedings of ICCR'2008.
  • Publication date: 2008/04/05

Links


See other articles from the proceedings (170)
See the conference proceedings