Trials with zeotropic refrigerants as replacements for R22 in an instrumented glycol-water chiller.
Author(s) : CORR S., GILBERT B., DEKLEVA T., LOW R., MURPHY F. T., DAVIES G.
Summary
A large number of measurements taken from an instrumented glycol-water process chiller are summarized for R22 and a number of zeotropic refrigerant blends. The range of materials used in the study includes 2 zeotropic binary blends of R32-R134a (30-70 and 25-75), and 2 zeotropic ternary blends of R32-R125-R134a (30-10-60 and 23-25-52). The information covers the evaporator temperature range -20 to 5 deg C and condenser range 27 to 41 deg C. Results include COP, capacity and discharge temperature for the chiller running on R22-mineral oil and HFC refrigerant blend-polyolester lubricant combinations. Over the temperature range of test, the HFC blends show comparable COP and capacity to R22 while exhibiting lower discharge temperatures.
Details
- Original title: Trials with zeotropic refrigerants as replacements for R22 in an instrumented glycol-water chiller.
- Record ID : 1995-0763
- Languages: English
- Source: Proceedings of the 1994 International Refrigeration Conference at Purdue.
- Publication date: 1994/07/19
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (73)
See the conference proceedings
Indexing
-
Themes:
HCFCs;
HFCs - Keywords: R134a; R32; R22; R125; Substitute; Zeotropic mixture; Oil; Glycol; Refrigerant
-
Zeotropic refrigerants in the real world: perfo...
- Author(s) : BRESNAHAN J. D., LOW R. E.
- Date : 1995/05/01
- Languages : English
- Source: 1995 AIRAH Conference Proceedings.
View record
-
Leistungbestimmung, Leckagenverhalten, Brennbar...
- Author(s) : ROBERTS N. A.
- Date : 1998/11/18
- Languages : German
- Source: DKV-Tagungsbericht 25. 1998, Würzburg.
View record
-
Isceon 59, une alternative intéressante.
- Author(s) : VOIGT A.
- Date : 1998/11/11
- Languages : French
- Source: 9e Y-Symposium Froid. Résumé des conférences.
View record
-
Performance evaluation of chlorine free zeotrop...
- Author(s) : PANNOCK J., DIDION D. A., RADERMACHER R.
- Date : 1992/07/14
- Languages : English
View record
-
The replacement of HCFC22 in refrigeration syst...
- Author(s) : HEWITT N. J., MCMULLAN J. T., MONGEY B.
- Date : 1994/09/21
- Languages : English
- Source: CFCs, the Day After.
- Formats : PDF
View record